    Figure * 3000 W AC-Input Power Supply




    3000 W Power Supply Specifications

    Table A-25 lists the specifications for the 3000 W AC-input power supply.

    Table A-25 3000 W Power Supply Specifications 

    Specification
    Description

    AC-input type

    Autoranging input with power factor correction (PFC).

    Note Power factor correction is a standard feature on all Catalyst 6500 series AC-input power supplies. PFC reduces the reactive component in the source AC current allowing higher power factors (typically 99 percent or better) and lower harmonic current components.

    AC-input voltage

    Low-line (120 VAC nominal)—85 VAC (min) to 132 VAC (max)

    High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)

    AC-input current

    16 A @ 200 VAC (3000 W output)

    16 A @ 100 VAC (1400 W output)

    AC-input frequency

    50/60 Hz (nominal) (±3% for full range)

    Branch circuit requirement

    Each chassis power supply should have its own dedicated, fused-branch circuit:

    For North America—20 A

    For International—Circuits sized to local and national codes

    All AC power supply inputs are fully isolated.

    Source AC can be out of phase between multiple power supplies in the same chassis, which means that PS1 can be operating from phase A and PS2 can be operating from phase B.

    For high-line operation, the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC.

    Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs, which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B.

    Power supply output capacity

    1400 W maximum (100-120 VAC)

    3000 W maximum (200-240 VAC)

    Power supply output

    100/120 VAC operation

    25.0 A @ +3.3 V

    5 A @ +5 V

    12 A @ +12 V

    27.89 A @ +42 V

    200/240 VAC operation

    25.0 A @ +3.3 V

    5 A @ +5 V

    12 A @ +12 V

    65.98 A @ +42 V

    Front panel power
    connector

    A two-pin male Molex connector is located in the lower right corner of the power supply front panel. The connector provides 42 VDC at a maximum of 17 A. This connector provides power to the WS-6509-NEB-UPGRD kit fan assembly through a power harness also provided in the kit. A hinged protective flap secured by a captive screw covers the connector when it is not in use.

    Output holdup time

    20 ms minimum

    kVA rating1

    3520 W (total input power) or 3.6 KVA (high-line operation)

    Heat dissipation

    12,046 BTU/hour (approx.)

    Weight

    15.8 lb (7.2 kg)

    1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch.


    Table A-26 lists the power supply LEDs and their meanings.

    Table A-26 3000 W AC-Input Power Supply LEDs 

    LED
    Meaning

    INPUT OK

    Green—Source AC voltage is OK. (Input voltage is 85 VAC or greater.)

    Off—Source AC voltage falls below 70 VAC, is not present, or the power supply is turned off.

    FAN OK

    Green—Power supply fan is operating properly.

    Off—Power supply fan failure is detected.

    OUTPUT FAIL

    Red—Problem with one or more of the DC-output voltages of the power supply.

    Off—DC-output voltages within acceptable margins.

    Note For proper operation of the OUTPUT FAIL LED, systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine. Systems with dual power supplies must have a minimum configuration of one fan tray, one supervisor engine, and one additional module. Failure to meet these minimum configuration requirements can cause a false power supply output fail signal.

    42V OK

    Green—42 VDC is present at the fan power connector.

    Off—42 VDC is not present at the fan power connector.


    3000 W Power Supply AC Power Cords

    Table A-27 lists the specifications for the AC power cords that are available for the 3000 W AC-input power supply. The table includes references to power cord illustrations.

     

    Note All 3000 W power supply power cords are 14 feet (4.3 meters) in length.


     

    Note All 3000 W power supply power cords have an IEC60320/C19 appliance connector at one end.


    Table A-27 3000 W Power Supply AC Power Cords

    Locale
    Power Cord
    Part Number
    AC Source Plug Type
    Cordset Rating
    Power Cord Reference Illustration

    Argentina

    CAB-7513ACR= or CAB-IR2073-C19-AR=

    IRAM 2073

    16 A, 250 VAC

    Figure A-31

    Australia, New Zealand

    CAB-AC-16A-AUS=

    AU20S3

    16 A, 250 VAC

    Figure A-46

    People's Republic of China

    CAB-AC16A-CH=

    GB16C

    16 A, 250 VAC

    Figure A-37

    Continental Europe

    CAB-AC-2500W-EU=

    CEE 7/7

    16 A, 250 VAC

    Figure A-41

    International

    CAB-AC-2500W-INT=

    IEC 309

    16 A, 250 VAC

    Figure A-42

    Israel

    CAB-AC-2500W-ISRL=

    SI16S3

    16 A, 250 VAC

    Figure A-34

    Japan, North America (nonlocking plug)
    200-240 VAC operation

    CAB-AC-2500W-US1=

    NEMA 6-20

    16 A, 250 VAC

    Figure A-43

    Japan, North America (locking plug)
    200-240 VAC operation

    CAB-AC-C6K-TWLK=

    NEMA L6-20

    16 A, 250 VAC

    Figure A-44

    Japan, North America
    100-120 VAC operation1

    CAB-7513AC=

    NEMA 5-20

    20 A, 125 VAC

    Figure A-36

    Power Distribution Unit (PDU)2

    CAB-C19-CBN=

    IEC 60320 C19

    IEC 60320 C20

    16 A, 250 VAC

    Figure A-47

    Switzerland

    CAB-ACS-16=

    SEV 5934-2 Type 23

    16 A, 250 VAC

    Figure A-45